Current Location:Home ›› Products ›› Sludgeinstrument ›› Ultrasonic sludge interface instrument

Ultrasonic sludge interface instrument

Function: split type

Protection level: IP65 for display instrument, IP68 for probe

Probe installation: according to range and probe selection

product details

一、Packaging & Delivery

Selling Units:  Single item

Single package size: : 39*26.5*16.5cm

Single gross weight:1.500 KG

二、The interface of ultrasonic sludge interface instrument and operation mode is as follows:

  说明: 液位计英文菜单主界面

 

      Running Mode  

Our products can be debugged through three keys on the panel. Then, the measured value is showed by LED.

                             

      ◇Enter to menu                  ◇Move the cursor

◇Confirm menu                   ◇Select the menu

◇Confirm parameter calibration  ◇parameter calibration

1 . After switched on of the sludge blanket, press the SET key for two second and enter the first level menu.

2. Measured Mode:

Two types: Measured water level and Measured Sludge blanket,

The factory default is Measured Sludge blanket.

3. The height value of probe input to the “reference zero”.(the height of probe is the distance from the launch of probe to the bottom)

image015.jpgimage016.jpg

Figure 1-1    Measured Water level                  Figure1-2    Measured Sludge blanket

 

三.Technical parameters:

Function

Split Type

Range

Conventional:5m、10m、15m、20m

Customized: 30m、40m、50m、60m、70m

Accuracy

1%~3%

Resolution

5mm or 0.5%(maximum)

Display

Chinese and English LED

Analog Output

4~20mA/750Ω load

Relay Output

 

Two group of Single Channel    AC 250V/ 8A or DC 30V/ 5A 

Status can be programmed

Power supply

Standard: 220V AC+15%  50Hz

Option:24VDC 120mA

Customize: 12VDC or battery

Environment

Temperature

LED : -20~+60℃,

Probe : 20~+80℃

Communication

Option:485,232 Communication(manufactures agreement)

Protection Grade

LED: IP65,

Probe: IP68

Cable Probe

 Standard 10m, the longest   is 100m

Probe installation

According to range and the type of probe

 

Power Consumption

Power supply:24V,

No relay: 100mA

Channel 1 of  Relay: 120mA;

Channel 2 of  Relay: 145mA;

Channel 3 of  Relay: 170mA;

Channel 4 of  Relay: 190mA;

The specific power is as follows:

 No relay:  24×100mA=2.4W;

Channel 1 of  Relay: 24×120mA=2.9W;

Channel 2 of  Relay: 24×145mA=3.5W;

Channel 3 of  Relay: 24×170mA=4.1W;

Channel 4 of  Relay: 24×190mA=4.6W;


四、Installation

 4.1 Installation Instructions

4.1.1 Please follow them as bellow when you choose the installation location:

1) Keep the sensor perpendicular to the dirt surface and the bottom surface.

2)The probe should be completely submerged in water and away from the wall at least 50 cm, if the wall is vertical up and down and the surface flat. If the wall is not flat, the distance is 100cm. If the wall is not up and down vertically, then you need to adjust according to the actual situation.

If the wall is rugged, or with some objects (brackets, pipes ), in order to avoid interference of measurement caused by the above objects, please increase the distance from it.

(3)There isn’t any obstacle in the emitting surface under of the probe, so the ultrasonic signal can’t block and reflect by obstacles

(4)The installation of probe should be away from the gas bubbles and floating solids which cased by Velocity mutation, so as to ensure precise and stable of measurement.

 

4.2. Mounting Dimensions

图片2_335.300.png  

The mounting dimension of split type  mm

说明: 1

Figure 4-4

The probe mounting dimension of the split type mm

V. Field cases:

10.jpg

Product application:

 

Mainly used in sewage plant, water plant, mine, water conservancy, power plant, chemical plant, steel plant

The monitoring of waterlogging and water, sewage quality, urban pipeline and rainfall station in the construction of smart city project; applicable to the monitoring of rainfall point of existing water conservancy projects, river water and rain monitoring, reservoir water and rain monitoring, flow station, irrigation area, open channel monitoring, etc.; automatic monitoring of water plant, on-line water quality monitoring and secondary water supply monitoring of smart water project; suitable for intelligent water project It is used for the monitoring of collapse and landslide points, debris flow and surface water level of geological disaster projects

VI. Manufacturer:

 